| TYPE |
Portable transformer winding resistance meter |
| PHYSICAL SPECIFICATIONS |
21” W x 17” H x 9” D (53 cm x 43 cm x 24 cm); Weight: 35 lbs (15.8Kg) |
| OPERATING VOLTAGE |
100 – 240 Vac, 50/60 Hz |
| RESISTANCE READING RANGE |
1 micro-ohm to 500 Ohms |
| ACCURACY |
1 – 19,999 micro-ohms: ±0.5% reading, ±1 count
20 – 999 milliohms: ±1% reading, ±1 count
1 -2000 Ohms: ±1.5% reading, ±1 count |
| TEST CURRENT |
1-40A in 1A increments |
| TEST VOLTAGE |
60 Vdc charging, 18V DC max during measurement |
| INPUT CHANNELS |
4 input channels for measuring resistance |
| DISPLAY |
Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels |
| PRINTER |
Built-in 2.5" wide thermal printer |
| INTERNAL DATA STORAGE |
256 static test records (each can contain up to 111 readings) and 120 dynamic test records |
| EXTERNAL DATA STORAGE |
Up to 999 test records on external USB Flash drive. |
| COMPUTER INTERFACES |
RS-232C, USB, Bluetooth |
| SAFETY |
|
| ENVIRONMENT |
Operating: -10oC to 50oC (15oF to +122oF)
Storage: (-30oC to 70oC (-22oF to +158oF) |
| HUMIDITY (MAX) |
90% RH @ 40 C (104 F) non-condensing |
| ALTITUDE (MAX) |
2000m (6562 ft) to full safety specifications |
| CABLES |
Four 50-foot test cables, one LTC control cable, one ground cable, one power cord, one USB cable |
| OPTIONS |
Shipping Case |
| WARRANTY |
One year on parts and labor |
| Specifications are valid at nominal voltage and ambient temperature of +25C (+77F). |