| TYPE |
Portable circuit-breaker analyzer |
| PHYSICAL SPECIFICATIONS |
14”W x 21 K” L x 8” D (35 cm x 53 cm x 20 cm); 15 lbs (6.8 Kg) |
| INPUT POWER |
100-240Vac, 3A, 50/60Hz |
| DRY-CONTACT INPUTS |
3 channels (9021-UC) or 6 channels (9100-UC). Channel can detect the main contact and resistor contact time. |
| TIMING WINDOWS |
1 second, 10 seconds, or 20 seconds |
| TIMING RESOLUTIONS |
±50 micro-seconds @ 1 sec. duration, ±500 micro-seconds @ 10 sec. duration, ±1.0 milli-seconds @ 20 sec. duration |
| TIMING ACCURACY |
0.05% of reading ±0.05 ms @ 1 second duration |
| DRY-CONTACT CHANNEL PROTECTION |
All contact inputs are grounded until test. Input channels are also protected against static discharge. |
| DRY-CONTACT DETECTION RANGE |
Closed: Less than 20 Ohm. Opened: greater than 5000 ohm |
| INSERTION RESISTOR DETECTION RANGE |
50 – 5,000 ohms |
| TRIGGER INPUT VOLTAGE |
Open/Close trigger voltage: 24 V – 300V DC or peak AC |
| VOLTAGE SENSING INPUT RANGE |
V1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC; record and print 3 timing events |
| BREAKER OPERATIONS |
Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open |
| BREAKER INITIATE CAPACITY |
30A, 250 Vac/dc max |
| INITIATE CURRENT READING RANGE |
one, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC |
| DIGITAL TRAVEL TRANSDUCER INPUTS |
3 channels, 200 ohm – 10K ohms |
| CONTACT TRAVEL POINT DIFFERENCE |
measures “slow-close” contact-point distances; results can be printed |
| DISPLAY |
back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light |
| PRINTER |
built-in 4.5” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results |
| INTERNAL TEST RECORD STORAGE |
Store up to 200 test records and 100 test plans |
| EXTERNAL TEST RECORD STORAGE |
USB Flash drive interface for external storage of test records and test plans |
| COMPUTER INTERFACES |
One USB port, optional Bluetooth wireless interface |
| PC SOFTWARE |
Windows? based Breaker Analysis software included with purchase price |
| CABLES |
furnished with full set of test leads |
| OPTIONS |
transportation cases (available for the CT-7000 S3 and travel transducers), on-line timing mode, dual ground testing mode, bluetooth interface |
| SAFETY |
|
| ENVIRONMENT |
Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F) |
| HUMIDITY |
90% RH @ 40°C (104°F) non-condensing |
| ALTITUDE |
2,000 m (6,562 ft) to full safety specifi cations |
| WARRANTY |
one year on parts and labor |
| Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F). |