MCE ADV

Project Description产品描述

上海山合海融商贸有限公司现有一只 MCE06ADV400 功率因素控制器现货提供,该型号可控制6回路,电压400V,随时可以发货。

Power factor controllers MCE ADV
MCE ADV功率因素控制器

Power factor controllers MCE-6 ADV (6 steps) and MCE-12 ADV (12 steps) are designed to measure the requirements of reactive energy of an installation and give the orders of connection and disconnection of capacitors so as to keep the set up cos φ.
功率因数控制器MCE-6 ADV(6路)和MCE-12 ADV(12路)是针对测量装置的无功功率要求而设计的,它给出电容器的连接与断开顺序,以保持设定的功率因素cosφ。

Plug and Play
即插即用

When a power factor controller is installed, a number of parameters need to be set up for a proper operation. Some of these parameters might be hard to know, such as, for example, the voltage phases or the correspondence of the measured current with its voltage, as well as the current transformer ratio. Controller MCE ADV incorporates a smart automatic process that detects the necessary parameters, such as:
当安装功率因数控制器时,需要设置多个参数以进行正确的操作。这些参数中的一些可能很难知道(获取),例如,电压相位或测量的电流与其电压的对应关系,以及电流互感器比。控制器MCE ADV结合了智能自动过程,可以检测必要的参数,例如:

  • C/K: calculates the ratio of the current transformer and the power of the smallest step.
    检测和计算电流互感器的比和最小阶的功率。
  • Phase: Identifies the voltage sequence and correspondence with the current. In other words, it identifies the UL1, UL2, UL3, when the current measured is IL1, IL2, IL3 and whether it has been connected in the opposite way.
    相位:识别电压序列和与电流的对应关系。换句话说,它识别UL1、UL2、UL3,当测量的电流是IL1、IL2、IL3以及它是否已经以相反的方式连接。
  • Number of stages installed and Program: by sequential connection of all steps it finds out how many steps are installed and then calculates the program, i.e., the power ratio between capacitors.
    安装级数和程序:通过顺序连接所有步骤,找出安装了多少步骤,然后计算程序,即电容器之间的功率比。

FEATURES 特征

  1. IMPROVED SETTING UP FOR COMMISSIONING
    改进调试准备

Phase
相位

Installation and polarity of the CT (Current Transformer). The regulator allows the user not to have to change phase location where the TC (X/5) is located and/or the reading direction/polarity. The adjustment can be made via the menu on the controller display.
CT(电流互感器)的安装和极性。款转器允许用户不必改变TC(X/5)所在的相位位置和/或读取方向/极性,可以通过控制器显示器上的菜单进行调整。

  1. READING OF INSTALLATION VALUES
    安装值读数
  • Current (A)电流
    Total RMS current (A) measured from the CT (X/5).
    从CT(X / 5)测量的总RMS电流(A)。
  • Voltage (V)电压
    RMS voltage (V).
    RMS电压
  • THD (%) in Current (A)电流中的总谐波分布
    Instantaneous harmonic distortion indicative of current present in the installation in %.
    瞬时谐波失真指示当前安装中的电流%
  • MAX (A) & (V) Recording最大电压和电流记录
    It records in memory the maximum system current and voltage values, starting from TC (X/5) and the capacitor bank voltage.
    记录从TC(x/5)和电容器组电压开始的最大系统电流和电压值。
  1. 通过LED和继电器进行事件报警

MCE ADV incorporates a LED and an output relay to warn in case that any of the following circumstances happens:
MCE ADV包含一个LED和一个输出继电器,当发生下列情况的任何一种情况时就发出报警:

  • Lack of compensation.
    缺乏补偿。
  • Over-compensation.
    过度补偿。
  • Over-voltage.
    过电压
  • Over-current.
    过电流
  • CT unplugged.
    电流互感器拔出。
  • Current below the limits.
    电流低于限值。

(Note: to perform alarm relay it is necessary to have available one step relay).
(注意:为了执行报警继电器,必须至少有一路可用的继电器)。

Tutorial Video

Loading...
Supply rated voltage
电源电压
230/400/480 V
Frequency range
频率范围
45 … 65 Hz (automatic adjustment)
自动调节
Power consumption
功率消耗
MCE ADV-6 –> 3VA (no relays) and 5,5VA (6 relays on)
MCE ADV-6 –> 3VA (无继电器) and 5,5VA (6路继电器全开)

MCE ADV-12 –> 4VA (no relays) and 8,5VA (12 relays on)
MCE ADV-12 –> 4VA (无继电器) and 8,5VA (12路继电器全开)

External current transformer
外部电流互感器
/5 A (not included)
Accuracy of voltage measurement
电压测量精度
1%
Working program selection
工作程序选择
1.1.1.1., 1.2.2.2., 1.2.4.4., 1.2.4.8. y 1.1.2.2.
Adjustment of cos φ
功率因素调节
0.85 Ind – 0.95 Cap (digital)
LCD Display
LCD显示屏
1 line x 3 digits x 7 segments + 20 icons
Lecture of cos φ
功率因素演示
LCD Display
LCD显示屏
Accuracy of cos φ measurement
功率因素测量精度
2% ± 1 digit
Adjustment of C/K factor
检查测试因素调节
0.02 …1 (digital)
Connection time between steps
回路间连接时间
4 … 999 seg.(10s default)
Reconnection time of capacitors
电容器重连接时间
5 times T connection
Climatic range
气候范围
-10/+50ºC
Wiring
布线
Connection terminal
接线端子
Degree of protection
防护等级
IP40 mounted on panel board (as per EN60529)
安装在面板上(根据EN60529标准)
Safety/Insulation
安全/绝缘
EN61010-1, Cat. III Environment 2
Dimensions
尺寸
144x144mm (hole 138x138mm)
Total depth
总深
60mm
Weight
重量
538g
Selection number of output relays
输出继电器的可选数量
MCE ADV-6: 6 relays
MCE ADV-12: 12 relays
Control strategy
控制策略
(program that minimizes the number of switching operations)
(最小化开关操作次数的程序)
Output relays contacts
继电器输出触点
4 A/ 250V AC1
Standards
标准
EN61010, EN61000-3-2, EN61000-3-3, EN61000-6-1, EN61000-6-3 and UL94

Other powers, voltages and frequencies on request.
其他功率,电压和频率可按要求定做。

FileDateSize
Datasheet
产品资料
11/04/20180.1 MB
Manual
说明书
30/05/20180.6 MB
Programming guide
设置指南
31/05/20180.6 MB