2820 EL ELCB Testers
Up To 1000mA
|
 |
|
|
FEATURES |
| |
Operating voltage 100-450V L-E. |
Rated current 999mA, at 317V AC/50Hz. |
Checks ELCB trip time and trip point (sensitivity). |
Auto-Off/Auto-Ranging. |
Phase angle selection (0 degree / 180 degree). |
Indicates tripping phase angle. |
Impact resistant enclosure. |
Over temperature shut-down. |
Transient protection. |
Suitable for heavy industrial use. |
Fused. |
, -1 CAT III 450V. |
|
OPERATING PRINCIPLES |
EARTH LEAKAGE TESTS |
The testers may be used to check the trip point (Test 1) of the ECLB or the trip time (Test 2). Test 1 is normally used on instantaneous ELCBs while Test 2 is normally used on inverse and fixed time-delay ELCBs. |
TEST PROCEDURE |
Test 1 - instantaneous ELCBs A ramp current, increasing at approximately 12 mA/s is introduced between L and E and the point at which the ELCB trips is recorded. To save time and reduce energy dissipation, the starting point of the ramp may be selected. |
Test 2 - inverse and fixed time delay ELCBs. Aconstant current is selected and injected between L-E and the tripping time is recorded. |
|
| SPECIFICATIONS |
| |
| Trip Current-Range |
0-1 A at 317V (Auto-Range Programmable) |
| Trip Current-Resolution |
1mA |
| Operating Voltage (L-E) |
100-450V |
| Phase Angle Setting |
0 degree and 180 degree selectable |
| Timer-Max |
99.999s |
| Timer-Resolution |
1mS |
| Typical Accuracy |
|
| Trip-Current |
+/- 1%rdg +/-1mA |
| Trip-Time |
+/- 1%rdg +/-1dgt |
| Voltage |
+/- 3%rdg +/-1dgt |
| Operating-Temperature-Humidity |
-10 degree C to + 40 degree C, 80% max relative humidity |
| Power Source |
1.5V (AA) x 8 batteries |
| Dimensions |
170(L) x 120(W) x 95(D) mm |
| Weight |
Approx. 800g (battery included) |
| Accessories |
Test leads |
| |
Shoulder belt |
| |
Instruction manual |
| |
Batteries |
|